Fujitsu AJY126LELDH VRF outdoor unit

Fujitsu · J

Fujitsu AJY126LELDH VRF outdoor unit

Heating
40 kW
Cooling
40 kW
Heats down to
-20 °C
Maximum indoor units
36

Recommended for rooms of 280 to 400 m²

Price on request

About the J series

The J VRF series consists of heat pump outdoor units for cooling and heating buildings with many smaller rooms. The manufacturer describes the smaller J-IV units as suitable for commercial premises housing several small shops and recommends the slim J-IVL units for mid-sized office buildings and hotels, while the larger models serve a large number of indoor units, making them suitable for educational buildings too. Multiple indoor units connect to one outdoor unit, and long permitted piping runs give freedom in system design. J-IVL units discharge air to the front and can be installed directly on the ground or on a wall, even in narrow passages, and their low operating noise suits densely populated areas.

Certified heating data

Numbers from independent certification, not from advertising. Each row holds for the exact combination measured.

The values hold for the reference combination; your system is assembled to measure and has different values.

Eurovent · air to air · cassette units

SCOP 3.53

Design load
31.9 kW
Rated heating capacity (+7 °C)
40 kW
At -7 °C, at least
28.22 kW
At -10 °C, at least
21.83 kW
Lowest temperature in the rating
-20 °C

For this climate the rating covers heating down to -20 °C, with measured output down to -10 °C; it is not the unit’s operating limit.

Measured combination: AJY126LELDH

View the certificate

Eurovent · air to air · ducted units

SCOP 4.53

Design load
28.3 kW
Rated heating capacity (+7 °C)
40 kW
At -7 °C, at least
25.03 kW
At -10 °C, at least
21 kW
Lowest temperature in the rating
-20 °C

For this climate the rating covers heating down to -20 °C, with measured output down to -10 °C; it is not the unit’s operating limit.

Measured combination: AJY126LELDH

View the certificate

The rating tests the unit on an imaginary reference house. The design load is what that house needs at the design temperature (−10 °C in the average European climate), not the unit’s capacity; where the unit falls short of it, the rating assumes an electric backup heater covers the difference. The “at least” figures show what the unit delivered to that house at the stated temperature, not the most it can give.

According to the manufacturer, the unit heats down to an outdoor temperature of -20 °C.

Technical data

Cooling capacity (kW)40
Heating capacity (kW)40
Outdoor unit noise (dB(A))63
RefrigerantR410A
Refrigerant charge (kg)11
Pipe, liquid12.7 mm
Pipe, gas28.58 mm
Maximum height difference (m)40
Outdoor unit, W × H × D (mm)1,080 × 1,638 × 480
Outdoor unit weight (kg)213
Heats down to outdoor (°C)-20
Maximum indoor units36

Manufacturer's data.

Documents

They open on the manufacturer's site.

Also known as: AJH126LELDH

Earlier codes of the same unit: AJY126LELBH, AJH126LELBH